| • Inputs and Outputs |
| Digital Inputs |
6 channels |
| Relay Outputs |
6 channels |
| • Digital Input |
| Sensor Type |
Wet Contact (NPN or PNP), Dry Contact |
| I/O Mode |
DI or Event Counter |
| Dry Contact |
• On: short to GND
• Off: open |
| Wet Contact |
• On: 0 to 3 VDC
• Off: 10 to 30 VDC |
| Isolation |
3K VDC or 2K Vrms |
| Counter Frequency |
250 Hz, power off storage |
| • Relay Output |
| Type |
Form A (N.O.) relay outputs, 5A |
| Contact Rating |
5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110 VAC |
| Inductance Load |
2 A |
| Resistance Load |
5 A |
| Breakdown Voltage |
500 VAC |
| Relay On/Off Time |
1500 ms (Max.) |
| Initial Insulation Resistance |
1G min. @ 500 VDC |
| Expected Life |
100,000 times (Typical) |
| Initial Contact Resistance |
30 milli-ohms (Max.) |
| Pulse Output |
0.3 Hz at rated load |
| • LAN |
| Ethernet |
2 x 10/100 Mbps switch ports, RJ45 |
| Protection |
1.5 KV magnetic isolation |
| Protocols |
Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP |
| • Power Requirements |
| Power Input |
24 VDC nominal, 12 to 36 VDC |
| Power Consumption |
188 mA @ 24 VDC |
| • Physical Characteristics |
| Wiring |
I/O cable max. 14 AWG |
| Dimensions |
27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in) |
| Weight |
under 200 g |
| • Environmental Limits |
| Operating Temperature |
Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
| Storage Temperature |
-40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity |
5 to 95% (non-condensing) |
| • Standards and Certifications |
| Safety |
UL 508 |
| EMI |
FCC Part 15 Subpart B Class A |
| EMS |
IEC 61000-4, IEC 61000-6 |
| Shock |
IEC 60068-2-27 |
| Freefall |
IEC 60068-2-32 |
| Vibration |
IEC 60068-2-6 |
| • MTBF (mean time between failures) |
| Time |
808,744 hrs |
| Database |
Telcordia (Bellcore) |
| • Warranty |
| Warranty Period |
2 years |